Error Message

Description

Sim4100:#34. Bad Seq. Sequence number reset.

Message sequence number incorrect. Check Simplex User Manuals, and
driver manuals. Contact FieldServer Technologies for additional support.

Sim4100:#36. FYI. Bad sim4100_func=%d in
MapDesc=<%s>

Check the CSV file for the correct Simplex function type.

Sim4100:#38. FYI. Bad sim4100_func=%d in
MapDesc=<%s>

Check the CSV file for the correct Simplex function type.

Sim4100:#39 FYI. Data abandoned! State not
recognized. Mapdesc=<%s>

Attribute was found, but State not found in driver table. Contact
FieldServer Technologies for additional support.

Sim4100:#40 FYI. Data abandoned! Array too
short.(%d) Mapdesc=<%s>

Check the CSV file Data Array lengths

Sim4100:#41 FYI. Data abandoned! Array too
short.(%d) Mapdesc=<%s>

Check the CSV file Data Array lengths

Sim4100:#43. Err. Can only monitor %d point(s)
for ClearAll

Contact FieldServer Technologies for additional support.

Sim4100:#44 FYI. ClearAll mapDesc's must be
passive

Map Descriptor function has been changed automatically

Sim4100:#45

FYI.

User

added

SHOW

attribute=<%s> offset=%d method=%d

Sim4100:#46 Err. No space. Driver rejects SHOW
attribute=<%s> offset=%d method=%d

No space is available in internal driver table. Contact FieldServer
Technologies for additional support.

Sim4100:#47 Err. Duplicate. Driver rejects SHOW
attribute=<%s> offset=%d method=%d

Duplicate found in internal driver table. Contact FieldServer Technologies
for additional support.

Sim4100:#48 FYI. User added SHOW attr
state=<%s> value=%d

Sim4100:#49 Err. No space. Driver rejects SHOW
attr state=<%s> value=%d

No space is available in internal driver table. Contact FieldServer
Technologies for additional support.

Sim4100:#50 Err. Duplicate. Driver rejects SHOW
attr state=<%s> value=%d

Duplicate found in internal driver table. Contact FieldServer Technologies
for additional support.

sim4100:#51 Err. Length must be specified and >
0.

Check the CSV file for the length fields.

SIM4100:#52 FYI. Incoming Abandoned. Node
offline

Check the CSV file for node definitions, Simplex hardware, and
connections. A device node appears to be offline. Contact FieldServer
Technologies for additional support.

Sim4100:#53. Md=<%s> Abandoned. Polling was
inhibited.

Obsolete. Contact FieldServer Technologies for support.

Sim4100:#54. Err. SeqNumber check disabled.

Sequence number checking was disabled. Check your password. Contact
FieldServer Technologies for support.

Sim4100:#55. Error. Bad Sim4100_Func=%d in
MD=<%s>

Check the CSV file for the correct Simplex function type.

Sim4100:#56

Not used.

Sim4100:#57* Err. Cant parse Login message.
Ignored.

The driver ignored Login messages. No corrective action is required. This
message is printed for your information only.

Sim4100:#58 FYI. You could have used an Array
called <%s> to expose diagnostic info.

This message is printed for your information only. It can safely be
ignored. For additional information read section “Appendix C.3.2 Driver
Exposed Stats”

Sim4100:#59 Err. Checkpoint. Report this to Tech
Support.

An internal driver diagnostic has been triggered. You must report this
error to FieldServer’s Technical Support.

Sim4100:#60 Err. MapDesc=%s. No Node.

Every Sim4100 Map Descriptor must be connected to a node. Ensure that
the parameter ‘Node_Name’ has been specified on the Map Descriptor.