FieldServer FS-8700-41 User Manual
Page 26
FS-8700-41 Simplex 4100 Driver Manual
Page 26 of 48
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Array
Posn
Attribute
Value
Filled
In4
Note
0
Not Defined
10
1
The value 10 represents the count of the number of attributes that were extracted from the response. It is not equal to the number of array
locations filled in because some attributes (e.g. Value) result in more than one array location being updated.
1
PRIMARY STATUS 14 (Normal)
1
#
2
PHYSICAL STATE
The un-filled-in locations are not updated by the driver when this response is analysed because the attributes corresponding to these
locations were not reported in the response to the query.
3
RAW STATE
4
ACTIVE STATE
5
ARMED STATE
6
ENABLED STATE 11 (Enabled)
1
7
UNVERIFIED
0
1
8
CURRENT DEVICE
4 (Correct
Device)
1
9
DEVICE
12 (On_Line)
1
10
TEST STATE
3 (Self test
normal)
1
11
PRESENT SENSITIVITY
SELECTED
14
AVERAGE
17
VALUE
0
1
18
-41
1
19
Room for up two three numbers for attributes like value, peak but in this case only two values are relevant for this device
20
PEAK
0
1
21
-41
1
22
Room for up two three numbers for attributes like value, peak but in this case only two values are relevant for this device
23
TROUBLE THRESHOLD
6 (Range
Normal)
1
24
OUTPUT STATE
25
OUTPUT STATUS
26
DETECTOR SOUNDER
27
ALARM TEMPERATURE
SELECTED=
135
1
30
DETECTOR RELAY
4
Locations marked with a 1 are updated when the driver analyses this response