beautypg.com

FieldServer FS-8700-41 User Manual

Page 46

background image

FS-8700-41 Simplex 4100 Driver Manual

Page 46 of 48

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

A3 NUMBER OF OLD (UNCLEARED) FIRE ALARMS

ANALOG 144-3-0

A4 NUMBER OF OLD (UNCLEARED) SUPERVISORIES ANALOG 144-4-0

A5 NUMBER OF OLD (UNCLEARED) TROUBLES

ANALOG 144-5-0

A6 CURRENT HOUR

ANALOG 144-6-0

A7 CURRENT MINUTE

ANALOG 144-7-0

A8 CURRENT SECOND

ANALOG 144-8-0

A9 CURRENT DAY

ANALOG 144-9-0

A10 CURRENT MONTH

ANALOG 144-10-0

A11 CURRENT YEAR

ANALOG 144-11-0

A12 CURRENT ACCESS LEVEL

ANALOG 144-12-0

A13 ACCESS LEVEL TIMEOUT

TIMER

144-13-0

A14 SYSTEM RESET WINDOW TIMER

TIMER

144-14-0

A15 SYSTEM RESET WINDOW TIMER SETPOINT

ANALOG 144-15-0

A16 DETECTOR RESET PULSE TIMER

TIMER

144-16-0

A17 4-WIRE RESET RELAY PULSE TIMER

TIMER

144-17-0

A18 FIRE ALARM CLEAR DELAY TIMER

TIMER

144-18-0

A19 FIRE ALARM CLEAR DELAY TIMER SETPOINT

ANALOG 144-19-0

A20 FIRE ALARM CLEAR PULSE TIMER

TIMER

144-20-0

A21 SYSTEM RESET PULSE TIMER

TIMER

144-21-0

A22 ALARM SILENCE INHIBIT TIMER

TIMER

144-22-0

A23 ALARM SILENCE INHIBIT TIMER SETPOINT

ANALOG 144-23-0

A24 FIRE ALARM CUTOUT TIMER

TIMER

144-24-0

A25 FIRE ALARM CUTOUT TIMER SETPOINT

ANALOG 144-25-0

A26 FIRE ALARM CUTOUT SILENCE PULSE TIMER

TIMER

144-26-0

A27 TROUBLE REMINDER CYCLE TIMER

TIMER

144-27-0

A28 TROUBLE REMINDER OFF-TIME SETPOINT

ANALOG 144-28-0

A29 TROUBLE REMINDER ON-TIME SETPOINT

ANALOG 144-29-0

A30 DOOR HOLDER ALARM DROP TIMER

TIMER

144-30-0

A31 DOOR HOLDER ALARM DROP TIMER SETPOINT ANALOG 144-31-0

A32 DOOR HOLDER BROWNOUT DROP TIMER

TIMER

144-32-0

A33 DOOR HOLDER BROWNOUT DROP TIMER SETPOINT

ANALOG 144-33-0

A34 SYSTEM STARTUP PULSE TIMER

TIMER

144-34-0

A35 FIRE ALARM AUDIBLE SIGNAL OPERATION

ANALOG 144-35-0

A36 FIRE ALARM VISUAL SIGNAL OPERATION

ANALOG 144-36-0

A37 ALARM VERIFICATION - RETARD TIME

ANALOG 144-37-0

A38 ALARM VERIFICATION - RESET TIME

ANALOG 144-38-0

A39 ALARM VERIFICATION - CONFIRMATION TIME

ANALOG 144-39-0

A40 ALARM VERIFICATION - TALLY LIMIT

ANALOG 144-40-0

A41 WALK TEST ABORT TIMEOUT SETPOINT

ANALOG 144-41-0

A42 WALK TEST REACTIVATE DELAY SETPOINT

ANALOG 144-42-0

A43 MONITOR ZONE ENABLE DELAY SETPOINT

ANALOG 144-43-0

A44 CODED INPUT TIMEOUT SETPOINT

ANALOG 144-44-0

A45 OFF TIME AFTER PNIS (NON-CONT.) CODES

ANALOG 144-45-0

A46 CITY CIRCUIT CONFIGURATION

ANALOG 144-46-0

A47 ALERT TONE/MSG AFTER MICROPHONE UNKEYED ANALOG 144-47-0

A48 TOTAL AUDIO CHANNELS

ANALOG 144-48-0

A49 CHANNEL 1 ROUTING

ANALOG 144-49-0