beautypg.com

Air for combustion and ventilation – FMI CCL3018PTA/NTA User Manual

Page 7

background image

www.fmiproducts.com

124971-01C

7

Example: Space size 20 ft. (length) x 16 ft.

(width) x 8 ft. (ceiling height) = 2,560 cu. ft.

(volume of space)

If additional ventilation to adjoining room

is supplied with grills or openings, add the

volume of these rooms to the total volume

of the space.

2. Multiply the space volume by 20 to determine

the maximum Btu/Hr the space can support.

________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

Example: 2,560 cu. ft. (volume of space) x

20 = 51,200 (maximum Btu/Hr the space can

support)

3. Add the Btu/Hr of all fuel burning appliances

in the space.

Vent-free fireplace

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________ Btu/Hr

Gas fireplace logs

__________ Btu/Hr

Other gas appliances* + _________ Btu/Hr

Total

= _________ Btu/Hr

* Do not include direct-vent gas appliances.

Direct-vent draws combustion air from the

outdoors and vents to the outdoors.

Example:

Gas water heater

__________ Btu/Hr

Vent-free fireplace

+ _________ Btu/Hr

Total

= _________ Btu/Hr

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

_______ Btu/Hr (maximum the space can

support)

_______ Btu/Hr (actual amount used)

Example: 51,200 Btu/Hr (maximum the

space can support)

79,000 Btu/Hr (actual amount of

Btu/Hr used)

The space in the example is a confined space

because the actual Btu/Hr used is more than the

maximum Btu/Hr the space can support. You

must provide additional fresh air. Your options

are as follows:
A. Rework worksheet, adding the space of an

adjoining room. If the extra space provides an

unconfined space, remove door to adjoining

room or add ventilation grills between rooms.

See Ventilation Air From Inside Building.

B. Vent room directly to the outdoors. See

Ventilation Air From Outdoors

, page 8

.

C. Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support,

the space is

an unconfined space. You will need no additional

fresh air ventilation.

WARNING: If the area in which

the heater may be operated does

not meet the required volume for

indoor combustion air, combus-

tion and ventilation air shall be

provided by one of the methods

described in the National Fuel

Gas Code, ANSI Z223.1/NFPA 54,

the International Fuel Gas Code,

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining

unconfined space. When ventilating to an

adjoining unconfined space, you must provide

two permanent openings: one within 12" of the

ceiling and one within 12" of the floor on the

wall connecting the two spaces (see options

1 and 2, Figure 2). You can also remove door

into adjoining room (see option 3, Figure 2).

Follow the National Fuel Gas Code, ANSI

Z223.1/NFPA 54, Air for Combustion and

Ventilation for required size of ventilation

grills or ducts.

AIR FOR COMBUSTION AND VENTILATION

Continued

40,000
39,000
79,000

Figure 2 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining

Room,

Option 1

12"

12"

This manual is related to the following products: