CAUTION: Avoid damage to

regulator. Hold gas regulator

with wrench when connecting it

to gas piping and/or fittings.

INSTALLATION

Continued

Figure 13 - Gas Connection

* Purchase the optional equipment shutoff

valve from your dealer.
** Minimum inlet pressure for purpose of input

adjustment.

3" Minimum

Sediment Trap

Gas

Regulator

Equipment Shutoff

Valve With 1/8" NPT

Tap*

Approved Flexible

Gas Hose (if allowed

by local codes)

Tee Pipe Cap

Joint Nipple

PROPANE/LP

From External Regulator

(11" W.C.** to 14" W.C.

Pressure)

NATURAL

From Gas Meter

(5" W.C.** to

10.5" W.C.

Pressure)

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip-

ing and connections, internal

and external to unit, for leaks

after installing or servicing. Cor-

rect all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply a

noncorrosive leak detection fluid

to all joints. Bubbles forming show

a leak. Correct all leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

heater. See guidelines under Con-

necting to Gas Supply, page 13.

CAUTION: Use only new, black

iron or steel pipe. Internally-tinned

copper tubing may be used in

certain areas. Check your local

codes. Use pipe of 1/2" diameter

or greater to allow proper gas vol-

ume to heater. If pipe is too small,

undue loss of volume will occur.

Installation must include an equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up.

NPT tap must be upstream from heater (see

Figure 13).
IMPORTANT: Install equipment valve in an

accessible location. The equipment shutoff

valve is for turning on or shutting off the gas

to the appliance.
Check your building codes for any special

requirements for locating equipment shutoff

valve to fireplaces.
Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could

result in clogged heater valves.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

We recommend that you install a sediment

trap in supply line as shown in Figure 14.

Locate sediment trap where it is within reach

for cleaning. Install in piping system between

fuel supply and heater. Locate sediment trap

where trapped matter is not likely to freeze.

A sediment trap traps moisture and contami-

nants. This keeps them from going into heater

controls. If sediment trap is not installed or is

installed wrong, heater may not run properly.