INSTALLATION

Continued

PRESSURE TESTING GAS SUPPLY

PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG

(3.5 kPa)

1. Disconnect appliance with its appliance

main gas valve (control valve) and equip-

ment shutoff valve from gas supply piping

system. Pressures in excess of 1/2 psig

will damage heater regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping by either opening

propane/LP supply tank valve for propane/

LP gas or opening main gas valve located

on or near gas meter for natural gas or

using compressed air.

4. Check all joints of gas supply piping system.

Apply a noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff

valve to gas supply. Check reconnected

fittings for leaks.

Test Pressures Equal To or Less Than

1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Fig-

ure 14).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve

for propane/LP gas or opening main gas

valve located on or near gas meter for

natural gas or using compressed air.

3. Check all joints from gas meter to equip-

ment shutoff valve for natural gas or pro-

pane/LP supply to equipment shutoff valve

for propane/LP (see Figures 15 and 16).

Apply noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

4. Correct all leaks at once.
PRESSURE TESTING HEATER GAS

CONNECTIONS

1. Open equipment shutoff valve (see Fig-

ure 15).

2. Open main gas valve located on or near

Figure 14 - Equipment Shutoff Valve

Equipment

Shutoff

Valve

Open

Closed

gas meter for natural gas or open pro-

pane/LP supply tank valve.

3. Make sure control knob of heater is in the

OFF position.

4. Check all joints from equipment shutoff

valve to thermostat gas valve (see Figures

15 and 16). Apply noncorrosive leak de-

tection fluid to all joints. Bubbles forming

show a leak.

5. Correct all leaks at once.
6. Light heater (see Operation, page 19).

Check all other internal joints for leaks.

7. Turn off heater (see To Turn Off Gas to

Appliance, page 20).

Figure 15 - Checking Gas Joints

(Propane/LP Gas Models)

Equipment

Shutoff Valve

Propane/LP

Supply Tank

Thermostat Gas Valve

Figure 16 - Checking Gas Joints (Natural

Gas Models)

Gas Meter

Equipment

Shutoff Valve

Thermostat Gas Valve