CONFIGURING THE FIELDSERVER AS A BACNET IP CLIENT
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a BACnet/IP Server.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for BACnet/IP communications, the driver independent FieldServer buffers need to be declared in
the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section,
and the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details
on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
5.1
Client Side Connection Parameters
Section Title
Connection
Column Title
Function
Legal Values
Adapter
Adapter Name
N1, N2
4
Protocol
Specify protocol used
BACnet_IP
Poll_Delay*
Time between internal polls
0-32000s; 0.25s
IP_Port*
Specify the UDP port that will be used to communicate
with other BACnet Client devices.
Any legal IP port value (1 - 65535);
47808
Example
// Client Side Connections
Connections
Adapter
, Protocol
, Poll_Delay
N1
, Bacnet_IP , 0500s
4