Appendix D. Reference

Appendix D.1. FieldServer Vendor ID

BACnet Vendor Name: Sierra Monitor Corporation
BACnet Vendor ID: 37

Appendix D.2. Object_Type Legal Values – Abbreviation Descriptions

AI

ANALOG_INPUT

AO

ANALOG_OUTPUT

AV

ANALOG_VALUE

BI

BINARY_INPUT

BO

BINARY_OUTPUT

BV

BINARY_VALUE

MI

MULTI_STATE_INPUT

MO

MULTI_STATE_OUTPUT

MV

MULTI_STATE_VALUE

NC

NOTIFICATION_CLASS_OBJECT

DEVICE DEVICE

Appendix D.3. Property Legal Values

Legal Value

Description

Object_Identifier

This property is a numeric code that is used to identify the object. It is unique within the
BACnet Device that maintains it.

Object_List

Relevant to Device Object Type. This property is a BACnetARRAY of Object_Identifiers, one
Object_Identifier for each object within the device that is accessible through BACnet
services. An Object_Identifier is composed of Object Type and Object Instance and must
be unique within a BACnet Device, e.g. Object Type = Analog Input, Object Instance = 3

Present_Value

This property contains the present value of the Input / Output / Value

Object_Name

Character string providing the name of a BACnet object. The set of characters used in the
Object_Name is restricted to printable characters. The Object_Name is determined by the
Map_Descriptor_Name.

Description

Character string describing a BACnet object. This can be defined by the user to give
additional detail about the Object.

Out_of_service

The Out_Of_Service property, of type BOOLEAN, is an indication whether (TRUE) or not
(FALSE) the physical input that the object represents is not in service. This means that the
Present_Value property is decoupled from the physical input and will not track changes to
the physical input when the value of Out_Of_Service is TRUE. In addition, the Reliability
property and the corresponding state of the FAULT flag of the Status_Flags property shall
be decoupled from the physical input when Out_Of_Service is TRUE. While the
Out_Of_Service property is TRUE, the Present_Value and Reliability properties may be
changed to any value as a means of simulating specific fixed conditions or for testing
purposes. Other functions that depend on the state of the Present_Value or Reliability
properties shall respond to changes made to these properties while Out_Of_Service is