Appendix d. reference, Appendix d.1. fieldserver vendor id, Appendix d.3. property legal values – FieldServer FS-8704-06 User Manual
Page 49: Appendix d.1, Appendix d.3

FS-8704-06 BACnet IP Driver Manual
Page 49 of 57
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix D. Reference
Appendix D.1. FieldServer Vendor ID
BACnet Vendor Name: Sierra Monitor Corporation
BACnet Vendor ID: 37
Appendix D.2. Object_Type Legal Values – Abbreviation Descriptions
AI
ANALOG_INPUT
AO
ANALOG_OUTPUT
AV
ANALOG_VALUE
BI
BINARY_INPUT
BO
BINARY_OUTPUT
BV
BINARY_VALUE
MI
MULTI_STATE_INPUT
MO
MULTI_STATE_OUTPUT
MV
MULTI_STATE_VALUE
NC
NOTIFICATION_CLASS_OBJECT
DEVICE DEVICE
Appendix D.3. Property Legal Values
Legal Value
Description
Object_Identifier
This property is a numeric code that is used to identify the object. It is unique within the
BACnet Device that maintains it.
Object_List
Relevant to Device Object Type. This property is a BACnetARRAY of Object_Identifiers, one
Object_Identifier for each object within the device that is accessible through BACnet
services. An Object_Identifier is composed of Object Type and Object Instance and must
be unique within a BACnet Device, e.g. Object Type = Analog Input, Object Instance = 3
Present_Value
This property contains the present value of the Input / Output / Value
Object_Name
Character string providing the name of a BACnet object. The set of characters used in the
Object_Name is restricted to printable characters. The Object_Name is determined by the
Map_Descriptor_Name.
Description
Character string describing a BACnet object. This can be defined by the user to give
additional detail about the Object.
Out_of_service
The Out_Of_Service property, of type BOOLEAN, is an indication whether (TRUE) or not
(FALSE) the physical input that the object represents is not in service. This means that the
Present_Value property is decoupled from the physical input and will not track changes to
the physical input when the value of Out_Of_Service is TRUE. In addition, the Reliability
property and the corresponding state of the FAULT flag of the Status_Flags property shall
be decoupled from the physical input when Out_Of_Service is TRUE. While the
Out_Of_Service property is TRUE, the Present_Value and Reliability properties may be
changed to any value as a means of simulating specific fixed conditions or for testing
purposes. Other functions that depend on the state of the Present_Value or Reliability
properties shall respond to changes made to these properties while Out_Of_Service is
TRUE, as if those changes had occurred in the physical input.