// ReadPropertyMultiple

Map_Descriptors

Map_Descriptor_Name , Object_Type , Property

, Function

, Data_Array_Name , Data_Array_Index , Node_Name , Address , Length , Write_Priority , Linked_Map_Descriptor

CMD RPM

, AO

, - , Rdbc

, DA RPM

, 9

, N1 1

, 1

, 2 , -

, -

Map_Descriptor_Name , Object_Type , Property

, Function , Data_Array_Name , Data_Array_Index , Node_Name , Address , Length , Write_Priority , Linked_Map_Descriptor

CMD RPM 3

, Device

, Max_Master

, Passive_Client , DA RPM

, 0

, N1 1

, 1

, 1

, -

, CMD RPM

CMD RPM 4

, Device

, Max_Info_Frames , Passive_Client , DA RPM

, 1

, N1 1

, 1

, 1

, -

, CMD RPM

CMD RPM 2

, AO

, -

, Passive_Client , DA RPM

, 2

, N1 1

, 8

, 4

, -

, CMD RPM

CMD RPM 1

, AO

, -

, Passive_Client , DA RPM

, 6

, N1 1

, 4

, 3

, -

, CMD RPM

Notes:

For the Present_Value property it is permissible to set a Map Descriptor length >1. This will cause a read of the Present_Value property of consecutive BACnet
objects of the type defined by this Map Descriptor

The number of properties that can be read or written at once is limited by the maximum APDU message length.

Message segmentation is not supported.

These map descriptors form part of the read transaction defined by
Map Descriptor CMD RPM above