Appendix b.4. bacnet specific error messages, Appendix b.5. bacnet error response decoding, Appendix b.5.1 – FieldServer FS-8704-06 User Manual
Page 41: Bacnet error class

FS-8704-06 BACnet IP Driver Manual
Page 41 of 57
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix B.4. BACnet Specific Error Messages
Message
Description
Cause
Suggested Resolution
Bacnet
IP
DLL
Temporarily out of
receive buffers
The FieldServer was flooded with more BACnet IP packets
than it could handle. This typically occurs when a
workstation discovers a large network resulting in many
Who-Is and I-Am broadcasts. The FieldServer will recover
from this, but some timeout errors could result.
Take action only if the error
is continuous in which case
the network load must be
analyzed and corrected.
Appendix B.5. BACnet Error Response Decoding
BACnet reports errors in the following format:
T02> 10/22 02:57 HEXDUMP : ERROR_PDU
T02> 10/22 02:57 0x19d2d 50 97 0f 91 02 91 2a
T02> 10/22 02:57 BACnet -> Unexpected ERROR_PDU : err_class=2 err_code=42
These can be decoded using the following tables:
Appendix B.5.1.
BACnet Error CLASS
Device
0
Object
1
Property
2
Resources 3
Security
4
Services
5