FS-8704-06 BACnet IP Driver Manual

Page 33 of 57

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Appendix A.9. Factors Determining the Reliability Property

The Reliability Property of a BACnet object in a Server configuration is determined as follows:

For Multistate Inputs, Outputs and Values, the Reliability property is set to MULTI_STATE_FAULT (9) when the
Present_Value of the object corresponds to an entry in the Fault_Values property of the object, as configured
by the State_Text table in the configuration file.

For all object types, the Reliability property is set to COMMUNICATIONS_FAILURE (12) when the responsible
Server Node is offline.

When neither Condition 1 nor Condition 2 is met, the Reliability property is set to NO_FAULT_DETECTED (0)