Appendix a.8.6, Setting the priority of intrinsic alarming – FieldServer FS-8704-06 User Manual

Page 31

background image

FS-8704-06 BACnet IP Driver Manual

Page 31 of 57

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Appendix A.8.6.

Setting the Priority of Intrinsic Alarming

Section Title
Map_Descriptors
Column Title

Function

Legal Values

Pri_To_Off_Normal* Priority for off normal events Refer to table below
Pri_To_Normal*

Priority for normal events

Refer to table below

Pri_To_Fault*

Priority for faults

Refer to table below


A BACnet EventNotification message contains a Priority field indicating the priority of the event being reported. The Priority values to be used are configured via the
Priority property of the Notification Class object, using the configuration file parameters Pri_to_offnormal, Pri_to_normal and Pri_to_fault, which determine the priorities
to be used respectively for all to-offnormal, to-normal and to-fault transitions reported via the Notification Class object.

Priority Values should be chosen as follows:

Alarm and Event Priority Network Priority
00-63

Life Safety Message

64-127

Critical Equipment Message

128-191

Urgent Message

192-255

Normal Message