Appendix a.8.6, Setting the priority of intrinsic alarming – FieldServer FS-8704-06 User Manual
Page 31

FS-8704-06 BACnet IP Driver Manual
Page 31 of 57
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix A.8.6.
Setting the Priority of Intrinsic Alarming
Section Title
Map_Descriptors
Column Title
Function
Legal Values
Pri_To_Off_Normal* Priority for off normal events Refer to table below
Pri_To_Normal*
Priority for normal events
Refer to table below
Pri_To_Fault*
Priority for faults
Refer to table below
A BACnet EventNotification message contains a Priority field indicating the priority of the event being reported. The Priority values to be used are configured via the
Priority property of the Notification Class object, using the configuration file parameters Pri_to_offnormal, Pri_to_normal and Pri_to_fault, which determine the priorities
to be used respectively for all to-offnormal, to-normal and to-fault transitions reported via the Notification Class object.
Priority Values should be chosen as follows:
Alarm and Event Priority Network Priority
00-63
Life Safety Message
64-127
Critical Equipment Message
128-191
Urgent Message
192-255
Normal Message