Appendix c.2.2, Example 1 – analog input, Appendix c.2.3 – FieldServer FS-8704-06 User Manual
Page 44: Example 2 – binary input, Appendix c.2.3. example 2 – binary input

FS-8704-06 BACnet IP Driver Manual
Page 44 of 57
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Appendix C.2.2.
Example 1 – Analog input
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Data_Type , Object_ID , Length , Event_Receiver_Name , Low_Alarm , High_Alarm , Event_Class , Ack_Required , Alarm_Deadband
ABB_vfd1_Output Frequency , ai1vfd1
, 1
, Passive , Bac11
, AI
, 1
, 1
, ADD_WS
, 20
, 30
, 5
, Yes
, 2
ABB_vfd1_Current
, ai1vfd1
, 2
, Passive , Bac11
, AI
, 2
, 1
, ADD_WS
, 0.5
, 1.5
, 5
, Yes
, 0.2
Appendix C.2.3.
Example 2 – Binary Input
Map_Descriptors
Map_Descriptor_Name
, Data_Array_Name , Data_Array_Offset , Function , Node_Name , Data_Type , Object_ID , Length , Event_Receiver_Name , Input_Alarm_State , Event_Class , Ack_Required
ABB_VFd1_RO_1 Status , bi1vfd1
, 0
, Passive , Bac11
, BI
, 1
, 1
, ADD_WS
, 1
, 5
, Yes
ABB_VFd1_Run Status , bi1vfd1
, 1
, Passive , Bac11
, BI
, 2
, 1
, ADD_WS
, 1
, 5
, Yes