beautypg.com

Appendix c.2.2, Example 1 – analog input, Appendix c.2.3 – FieldServer FS-8704-06 User Manual

Page 44: Example 2 – binary input, Appendix c.2.3. example 2 – binary input

background image

FS-8704-06 BACnet IP Driver Manual

Page 44 of 57

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Appendix C.2.2.

Example 1 – Analog input

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Data_Type , Object_ID , Length , Event_Receiver_Name , Low_Alarm , High_Alarm , Event_Class , Ack_Required , Alarm_Deadband
ABB_vfd1_Output Frequency , ai1vfd1

, 1

, Passive , Bac11

, AI

, 1

, 1

, ADD_WS

, 20

, 30

, 5

, Yes

, 2

ABB_vfd1_Current

, ai1vfd1

, 2

, Passive , Bac11

, AI

, 2

, 1

, ADD_WS

, 0.5

, 1.5

, 5

, Yes

, 0.2

Appendix C.2.3.

Example 2 – Binary Input

Map_Descriptors

Map_Descriptor_Name

, Data_Array_Name , Data_Array_Offset , Function , Node_Name , Data_Type , Object_ID , Length , Event_Receiver_Name , Input_Alarm_State , Event_Class , Ack_Required

ABB_VFd1_RO_1 Status , bi1vfd1

, 0

, Passive , Bac11

, BI

, 1

, 1

, ADD_WS

, 1

, 5

, Yes

ABB_VFd1_Run Status , bi1vfd1

, 1

, Passive , Bac11

, BI

, 2

, 1

, ADD_WS

, 1

, 5

, Yes