Appendix A.7. BACnet State Text Preload

BACnet Multistate Objects have a State_Text property. This property is defined as an array of character strings representing descriptions of all possible states
of the Present_Value. The number of descriptions matches the number of states defined in the Number_Of_States property. The Present_Value, interpreted as
an integer, serves as an index into the array.

When Multistate Objects are configured on a BACnet server it is necessary to define the State_Text property. This section illustrates how to define the
State_Text character strings and how to associate these definitions with Multistate Server Map Descriptors.

The maximum permitted length of any State_Text string is 50 characters.

Appendix A.7.1.

Method 1 – Using an Offset/User Table:

//set up a look up table

Offset_Table

Offset_Table_Name

, Table_String

, Table_Index_Value

FIRE_ALRM_TEXT

, SYSTEM READY

, 1

FIRE_ALRM_TEXT

, ALARM , 2

FIRE_ALRM_TEXT

, MAINTENANCE

, 3

FIRE_ALRM_TEXT

, OFF-LINE , 4

FIRE_ALRM_TEXT

, IN SERVICE , 5

FIRE_ALRM_TEXT

, OTHER , 6

Data_Arrays

Data_Array_Name , Data_Format , Data_Array_Length
DA_MI_01

, UINT16

, 100

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Object_Type , Object_Instance , Length , State_Text_Array
CMD_MI_01

, DA_MI_01

, 0

, Passive , N1 11

, MI

, 1

, 1

, Fire_Alrm_Text

Valid values are 1
to 16.