Server side connection parameters, Server side node parameters – FieldServer FS-8704-06 User Manual
Page 14

FS-8704-06 BACnet IP Driver Manual
Page 14 of 57
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
6.2
Server Side Connection Parameters
Section Title
Connections
Column Title
Function
Legal Values
Adapter
Adapter Name
N1, N2
5
Protocol
Specify protocol used
BACnet_IP
Connection_Type*
Specify if this Connection should act as a BBMD Server on the
network. Refer to Appendix A.5 for more information.
BBMD, -
IP_Port*
Specify the UDP port that will be used to communicate with
other BACnet Client devices.
Any legal IP port value (1
- 65535); 47808
Example
// Server Side Connections
Connections
Adapter
, Protocol
, Connection_Type
N1
, Bacnet_IP , BBMD
6.3
Server Side Node Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up
to
31
alphanumeric
characters
Node_ID
BACnet station address of physical Server node
0 - 4194303
Protocol
Specify protocol used
BACnet_IP
Node_Option*
Enable or disable COV for this Node. Refer to Appendix A.8 for
further information.
COV_Enable,
COV_Disable, -
Node_Type*
Specific to Trane applications. The Node type can be defined.
Refer to Appendix C.2
BCU,
Summit
Workstation, -
Disabled_Services*
Certain BACnet Services can be disabled on a BACnet Server Node
when specific requirements necessitate this. Refer to Appendix
A.12 for more information.
-, WPM, COV
Model_Name*
Sets the Model Name Property of the Device Object
Up
to
32
alphanumeric
characters
5 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.