6.2

Server Side Connection Parameters

Section Title
Connections
Column Title

Function

Legal Values

Adapter

Adapter Name

N1, N2

5

Protocol

Specify protocol used

BACnet_IP

Connection_Type*

Specify if this Connection should act as a BBMD Server on the
network. Refer to Appendix A.5 for more information.

BBMD, -

IP_Port*

Specify the UDP port that will be used to communicate with
other BACnet Client devices.

Any legal IP port value (1
- 65535); 47808


Example

// Server Side Connections

Connections

Adapter

, Protocol

, Connection_Type

N1

, Bacnet_IP , BBMD

6.3

Server Side Node Parameters

Section Title
Nodes
Column Title

Function

Legal Values

Node_Name

Provide name for Node

Up

to

31

alphanumeric
characters

Node_ID

BACnet station address of physical Server node

0 - 4194303

Protocol

Specify protocol used

BACnet_IP

Node_Option*

Enable or disable COV for this Node. Refer to Appendix A.8 for
further information.

COV_Enable,
COV_Disable, -

Node_Type*

Specific to Trane applications. The Node type can be defined.
Refer to Appendix C.2

BCU,

Summit

Workstation, -

Disabled_Services*

Certain BACnet Services can be disabled on a BACnet Server Node
when specific requirements necessitate this. Refer to Appendix
A.12 fo
r more information.

-, WPM, COV

Model_Name*

Sets the Model Name Property of the Device Object

Up

to

32

alphanumeric
characters

5 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.