5

CONFIGURING THE FIELDSERVER AS A LUTRON MACHINE CLIENT

For a detailed discussion on FieldServer configuration, please refer to the FieldServer instruction manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a Lutron eLumen panel.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Lutron eLumen communications, the driver independent FieldServer buffers need to be
declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side
Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors”
section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1

Client Side Connection Parameters

Section Title
Connections
Column Title Function

Legal Values

Port

Specify which port the device is connected to the FieldServer P1-P8, R1-R2

1

Protocol

Specify protocol used

eLumen

Baud*

Specify baud rate

9600 (Vendor limitation)

Parity*

Specify parity

None (Vendor limitation)

Data_Bits*

Specify data bits

8 (Vendor limitation)

Stop_Bits*

Specify stop bits

1 (Vendor limitation)

Poll _Delay*

Time between internal polls

0-32000 seconds, 1 second


Example

// Client Side Connections

Connections
Port , Protocol , Baud , Parity , Poll_Delay
P1

, eLumen

, 9600 , None

, 0.100s

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available