FS-8700-97 Lutron Machine Manual

Page 15 of 24

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Preloads
Data_Array_Name , Preload_Data_Format , Preload_Data_Value , Location

// Analog Output1 Object ID 1
Zone_pars_AO1

, Uint16

, 0

, 0

Zone_pars_AO1

, Uint16

, 1

, 1

// Analog Output1 Object ID 2
Zone_pars_AO1

, Uint16

, 2

, 2

Zone_pars_AO1

, Uint16

, 3

, 3

5.3.9 Map Descriptor Example 6 - Analog Output 2 (Zone and Area Machine)

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will execute one of multiple scripts on the Lutron eLumen panel. The value
written into the Analog Output Data Array is used as an offset into the Data Array defined under “DA_Lut_List” to retrieve a script number. Script numbers range from 0
to 65535.

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name

, Data_Type , Object_ID , Length , Relinquish_Default

SMD512_AO

, Analog_Output

, 512

, Passive

, Virtual_BCU_11 , AO

, 513

, 512

, 0

Lutron Machine Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Grafik_Command , DA_Lut_List

, DA_Lut_List_Offset , Length , Multi_Scripts_Length

Run_script_512

, Analog_Output

, 512

, Awt

, LUT_GRF6_0 , Run_Script_Multi , Scr_Lst_AO2_512 , 0

, 1

, 10