FieldServer Lutron Machine FS-8700-97 User Manual
Page 19
FS-8700-97 Lutron Machine Manual
Page 19 of 24
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
5.3.12 Map Descriptor Example 8 - Analog Input (Zone Machine)
A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the intensity to which a given zone is set on the Lutron eLumen panel.
The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the zone intensities. The intensity value returned is scaled to a percentage value
(0 to 100%). Zone numbers range from 0 to 511.
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name
, Data_Type , Object_ID , Length , Relinquish_Default
SMD00_AI
, Analog_Input
, 0
, Passive
, Virtual_BCU_11 , AI
, 1
, 512
, 0
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Grafik_Command , Zone , Length
Zone_inta_0
, Analog_Input
, 0
, Arco
, LUT_GRF6_0 , Zone_Intensity
, 0
, 512