5.3.8 Map Descriptor Example 5 - Analog Output 1 (Zone Machine)

A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command a zone on the Lutron eLumen panel to the written intensity.
Intensities are written as a percentage value (0 to 100%).

BACNet IP Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name

, Data_Type , Object_ID , Length , Relinquish_Default

SMD000_AO

, Analog_Output

, 0

, Passive

, Virtual_BCU_11 , AO

, 1

, 512

, 0

Lutron Machine Map Descriptor

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Grafik_Command , Zone , DA_Lut_Parms

, DA_Lut_Parms_Offset , Length

Fade_to_lvl_0

, Analog_Output

, 0

, Awt

, LUT_GRF6_0 , Fade_Zone

, 0

, Zone_Pars_AO1 , 0

, 512

The zone field must be used to indicate the start zone number that will be associated with the first element of the Data Array specified under Data_Array_Name . Zone
numbers increase with the Length field in association with increasing offset into the Data Array.

Fade and Delay times per zone must be preloaded into the Data Array specified under “DA_Lut_Parms”:

Analog Output1 Settings Setup

All values are in decimal ( 0 - 65535 )

Fade time in even locations, Delay time in uneven locations

Fill in time values under Preload_Data_Value