5.3.10 Map Descriptor Example 7 - Analog Input (Area Machine)
A read from the Analog Input Data Array which is shared by a BACNet IP Map Descriptor will return the last scene selected in a given area on the Lutron eLumen panel.
The Lutron Machine Map Descriptor regularly polls the Lutron eLumen panel to retrieve the scene numbers.
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptors_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name
, Data_Type , Object_ID , Length , Relinquish_Default , Data_Array_Low_Scale , Data_Array_High_Scale , Node_Low_Scale , Node_High_Scale
SMD00_AI
, Analog_Input
, 0
, Server
, Virtual_BCU_11 , AI
, 1
, 1
, 0
, 0
, 100
, 0
, 100
The last scene value may be scaled:
Analog Input Settings Setup
All values are in decimal ( 0 - 65535 )
Insert a first available scene number under the Data_Array_High_Scale field for each Object ID or use the scale fields as desired to scale scene numbers.
Object IDs are contiguous
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Grafik_Command , Area , Length
Last_scene_0
, Analog_Input
, 0
, Arco
, LUT_GRF6_0 , Area_Status
, 0
, 512