2 space requirements, Space requirements, Installation requirements – FUJITSU XG2600 User Manual
Page 30: Check-list

XG2600 Hardware Guide
Chapter 2 Installation
Requirements for Installation Environment
30
Installation Requirements
The product is specifically designed for rack-mounting.
Check-list
Check the following items.
2.1.2
Space Requirements
When installing the switch and providing maintenance, ensure the space below is maintained.
Ensuring the Space for Installation (Maintenance) of the Switch
Internal cooling fans of the switch allow the air intake and exhaust performed at both at the Port Side and Fan Unit Side.
Ensure the indicated space below and do not put anything which avoids airflow.
Check Item
Check Result
Nothing is put on the switch.
Vents are not obstructed.
The switch is not located on the table or not stuck on another switch.
The switch is not located under direct sunshine, near heating appliance, under high humidity
or in a dusty area..
The switch is not located on unstable places where vibrating, or tilting.
"About Warning Descriptions" has been thoroughly read
Reference
Reference
rack
300mm or more
800mm
800mm
XG2600
90mm
or more
150mm
or more
Back space for
the maintenance
Space for the
maintenance/
installation
Space for the
maintenance/
installation
300mm or more
Front space for
the maintenance
19" rack Width
19" rack
Depth