Ups does not start, Ups operates on battery only, Ups does not provide the expected backup time – HP R1500 User Manual
Page 30: 30 ups operates on battery only, 30 ups does not provide the expected backup time
![background image](/manuals/100258/30/background.png)
Troubleshooting 30
Condition
Power On
LED
(green)
On Battery
LED
(yellow)
Overload
LED
(red)
General
Alarm LED
(red)
Audible alarm
Can alarm
be silenced
("
On battery—No
utility power
Off On Off Off On— 4 second
beep
Yes
On battery—Battery
voltage condition
Flashing Off
Off
Flashing On—Continuous Yes
On battery—
Overload condition
Off On On Off On—1 second
beep
No
On battery—Output
voltage is out of
range
Off Flashing
Off Flashing
On—Continuous
No
On battery—Output
wave is abnormal
Flashing Flashing Off
Flashing On—Continuous No
For the location of individual LEDs, see "UPS front panel LED indicators (on page
)."
UPS does not start
Action:
1.
Be sure that the power cord is plugged in to a utility power receptacle.
2.
Check the power source at the utility power receptacle.
3.
Allow the UPS batteries to charge for 24 hours.
UPS operates on battery only
Action:
1.
Save your work.
2.
Power down the load devices connected to the UPS output receptacles.
3.
Remove one or more load devices to reduce the power requirements.
4.
Be sure the UPS configuration matches the utility voltage. Refer to "Selecting the UPS voltage
configuration (on page
)."
UPS frequently switches between utility and battery power
Action:
1.
Check the input voltage and reconfigure the UPS ("
Selecting the UPS voltage configuration
2.
Contact a qualified electrician to verify that the utility power is suitable for the UPS.
UPS does not provide the expected backup time
Action: