beautypg.com

Troubleshooting, Led and audible alarm troubleshooting – HP R1500 User Manual

Page 29

background image

Troubleshooting 29

Troubleshooting

In this section

LED and audible alarm troubleshooting..................................................................................................... 29
UPS does not start .................................................................................................................................. 30
UPS operates on battery only...................................................................................................
................ 30
UPS frequently switches between utility and battery power ......................................................................
.... 30
UPS does not provide the expected backup time ..................................................................................
...... 30
UPS cannot communicate with the host computer ....................................................................................... 31
UPS emits a slight clicking noise..............................................................................................
................. 31
Site Wiring Fault LED is red ...................................................................................................
.................. 31

LED and audible alarm troubleshooting

Condition

Power On
LED

(green)

On Battery
LED

(yellow)

Overload
LED

(red)

General
Alarm LED

(red)

Audible alarm

Can alarm
be silenced
("

Silencing

an audible
alarm

" on

page

22

)?

UPS operating from
utility

On

Off

Off

Off

No audible alarm N/A

Buck mode (high
input voltage)

On

Off

Off

Off

No audible alarm N/A

Boost mode (low
input voltage)

On

Off

Off

Off

No audible alarm N/A

Over temperature
condition

On On Off Flashing

On—Continuous

No

Battery test failure

Off

On

Off

Flashing

On—Continuous

Yes

Fan failure

On

Off

Off

Flashing

On—Continuous

No

Output short circuit

On

On

On

Flashing

On—Continuous

No

Power up failure
from a DC start—Low
battery (no utility
power)

Flashing Flashing Flashing Flashing On—3 beeps/10

seconds

No

Low battery (no utility
power)

Off Flashing

Off Off On—2 second

beep

No

Online—UPS power
capacity exceeded

On Off On Off On—1 second

beep

No

Overload timeout

Off

Off

On

Flashing

On—Continuous

No

On battery—Input
voltage is out of
range

On On Off Off On—2 second

beep

Yes