Testing the new battery module – HP R1500 User Manual

Page 27

background image

Maintenance 27

4.

Remove the battery bracket.

5.

Remove the UPS battery modules.

IMPORTANT: Do not pull the battery leads when removing or installing the batteries.

To replace the component, reverse the removal procedure.

IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to devices. The

batteries charge to:

90% of their capacity within 4 hours

100% of their capacity within 24 hours

Testing the new battery module

After installing the new battery module, press the Test/Alarm Reset button. For information on initiating a
self-test, see "Initiating a self-test (on page

22

)."

IMPORTANT: The UPS does not execute a self-test until the batteries are 90 percent charged.