71

A/I Module Offset Correction

The Analog Input module offset correction menu option

gives the user the ability to offset any input on any A/I

module for up to forty (40) inputs. Input correction curves

can also be applied to inputs 1 through 40. The offset can

be in degrees + or -, and it is typically used to

compensate for incorrect T/C wires.

Enable Offsets for Aux AIB

This option will determine if the offsets entered will be

applied on the inputs. The options are: Yes or No.

Input 1 – Input 40

This will be the offset for the specified input. The range of

the offsets is –50.0 to 50.0.

Input 1 Correction – Input 40 Correction

This will allow the user to enter a correction curve, if desired, to inputs 1 through 40. The options are: Not

Used, Curve 1 – Curve 7.

Aux Setpoint Configuration

Aux Setpoint Configuration is an automatic setpoint

retransmission with a corresponding custom offset and

delay to one or more of the first 3 configured slave

instruments. The delay is in minutes and is only active

when the setpoint is dropped. This feature would most

commonly be used to keep the alarm setpoint of an

overtemp tracking the furnace's main setpoint (with

offset). The delay allows the furnace time to cool below

the level specified so that there is no overtemp alarm

when the furnace is cooling.

Note: If the setpoint is 0, then the retransmission is

blocked

.

T/C Extension Correction Curves

This menu option will allow the user to set up to three

TC correction curves for the 9205 controller, as well

as three auxiliary correction curves (extension curves).

Clicking on the desired curve will display the curve

edit form.

Note: If the first “Temp” value and the first

“Error” value are both zero, then the curve will not be

set

. The user can enter up to ten “Temp”/“Error”

combinations.

The range for the “Temperature” field is –32768 to

32767.

The range for the “Error” field is –32768.000 to

32767.000.