Series 9205 Operations Manual Rev A

140

Slave Instrument Mapping

The following tables can be used as a reference for retrieving information such as the PV, setpoint, etc from

a slave instrument. The slave instrument information will have a base offset based on the instrument

number that is assigned. The base offset can be determined using the following formula:

Base Offset = (Instrument Number * 100) + 900

For example, the base offset for instrument 1 would be 1000 → (1 * 100) + 900 – and the base offset for
instrument 7 would be 1600 → (7 * 100) +900. The slave instruments will be split into three sections:

Atmosphere Instruments, Temperature Instruments, and Events Instruments. The layout for each

instrument will be the same:

Controller – The type of controller the slave instrument is – i.e. AC20, Series 9200, etc.

Source Location – The register

in the controller

where the specified value is located.

Note: These

will be added on to the base offset of the instrument (see above section)

. For example, the source

location for %C actual for an AC20 is 11. For instrument 1, the register to find the %C actual would
be 1011 → the base offset for instrument 1 is 1000, plus the source location of 11.

Write Register – The register

within the slave instrument

where the value will be written.

Read Scale – Any value read in from an instrument will be divided by this number for display

purposes only.

Write Scale – Any value written to an instrument will be multiplied by this number for display

purposes only.

Description – This will be a brief description of what the value is, i.e. %C actual, Setpoint, etc.

Atmosphere Instruments


Controller

Source

Location

Write

Register

Read

Scale

Write Scale

Description

AC20

11

123

1

1

%C Actual

(Modbus Mode)

29

138

1

1

%C Setpoint

13

125

1

1

Probe Temperature

10

122

1

1

Probe Millivolts

20

130

10

10

%C Percent Output

34

142

1

1

CO Factor or Equivalent

35

143

1

1

H Factor or Equivalent

12

124

1

1

Dew Point

36

144

10

10

O

2


Controller

Source

Location

Write

Register

Read

Scale

Write Scale

Description

Yoko 750

2

2

1

1

%C Actual

(Modbus Mode)

3

100

1

1

%C Setpoint

20

19

1

1

Probe Temperature

10

122

1

1

Probe Millivolts

4

4

10

10

%C Percent Output

0

0

1

1

CO Factor or Equivalent

0

0

1

1

H Factor or Equivalent