Super Systems 9205 Series User Manual
Page 160
Series 9205 Operations Manual Rev A
159
This opcode is used to enable a low limit alarm on the temperature or atmosphere. This alarm remains
active until the program ends.
The Temperature Setpoint is the setpoint to send for the temperature process variable. The range is -301
(disable) – 30000.
The Atmosphere Setpoint is the setpoint to send for the atmosphere process variable. The range is -0.01
(disable) to 99.99.
LOW_PO
Temperature PO Value
Atmosphere PO Value
N/A
This opcode is used to enable a low limit alarm on the temperature or atmosphere percent output.
The Temperature PO Value is the high limit point for the temperature percent output. The range is -101
(disable) to 100.
The Atmosphere PO Value is the high limit point for the temperature percent output. The range is -101
(disable) to 100.
This alarm remains active until the program ends.
LTC_SET
T/C Map
T/C Map
Load TC Enable
This opcode sets the active load T/C map for the furnace. Checking the box next to the T/C number selects
the T/C. The options are off, on, or on + alarms.
This Opcode is the same as Zone/Load TC Setup via the Menu options (see sections on Zone/Load TC Setup)
except that it selects thermocouples from the recipe. This may be helpful when certain recipes require
three Load TCs and other require six Load TCs.
MEVT_IN_0
Temperature Setpoint
Event Mask
Event ON/OFF Bitmap
This opcode waits for multiple input events 0 through 15.
The Temperature Setpoint is an optional setpoint to send down. The range is -301 (disable) – 30000.
The Event Mask is the events to enable, which is the events affected. The options are: 0 – 15.
The Event ON/OFF Bitmap field will allow the user to select the bitmap for the event ON/OFF, which will set
the final condition of the events in the event mask. The opcode ignores the bits not in the enabled events
and waits on the bits specified in the bitmap. The options are: 0 – 15.
MEVT_IN_1
Temperature Setpoint
Event Mask
Event ON/OFF Bitmap
This opcode waits for multiple input events 16 through 31.
The Temperature Setpoint is an optional setpoint to send down. The range is -301 (disable) – 30000.
The Event Mask is the events to enable, which is the events affected. The options are: 0 – 15.
Note – Even
though the events listed are 0 – 15, they correspond to 16 – 31
.
The Event ON/OFF Bitmap field will allow the user to select the bitmap for the event ON/OFF, which will set
the final condition of the events in the event mask. The opcode ignores the bits not in the enabled events
and waits on the bits specified in the bitmap. The options are: 0 – 15.
Note – Even though the events listed
are 0 – 15, they correspond to 16 – 31
.
MEVT_OUT_0
Temperature Setpoint
Event Mask
Event ON/OFF Bitmap
This opcode will set multiple output events 0 through 15.
The Temperature Setpoint is an optional setpoint to send down. The range is -301 (disable) – 30000.
The Event Mask is the events to enable, which is the events affected. The options are: 0 – 15.