Series 9205 Operations Manual Rev A
155
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the
SET_WAIT
opcode.
GDELAY
N/A
N/A
Delay Time
This opcode is a guaranteed short delay. It guarantees on the temperature loop unless the load TCs are
enabled, in which case it guarantees against the load TC map for the specified number of seconds.
The Delay Time is from 1 – 500 seconds.
GHDELAY
N/A
N/A
Delay Time
This opcode is a guaranteed high short delay opcode. The temperature process value must be below the
high limit deviation band to allow the delay timer to run. If the temperature process value goes out of the
deviation band, then the delay timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.
The Delay Time is from 1 – 500 seconds.
GHSOAK
N/A
Wait Limit
Soak Time
This is a guaranteed soak high opcode. The temperature process value must be above the deviation band to
allow the soak timer to run. If the temperature process value goes out of the deviation band, then the soak
timer will stop and wait until the temperature process value comes back into the deviation band before
starting up again.
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 167,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the
SET_WAIT
opcode.
GHZDELAY
N/A
N/A
Delay Time
This is a guaranteed high short delay opcode for a zone. The temperature process value must be below the
high limit deviation band to allow the delay timer to run. If the temperature process value goes out of the
deviation band, then the delay timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.
The Delay Time is from 1 – 500 seconds.
GHZSOAK
N/A
Wait Limit
Soak Time
This is a guaranteed soak high opcode for a zone. The temperature process value must be below the high
limit deviation band to allow the soak timer to run. If the temperature process value goes out of the
deviation band, then the soak timer will stop and wait until the temperature process value comes back into
the deviation band before starting up again.
The Wait Limit is the wait time, in Hours: Minutes format, for the wait limit. The Hours range from 0 – 533,
and the Minutes range from 0 – 59.
The Soak time is the total time, in Hours:Minutes format, for the soak to run. The Hours range from 0 –
166, and the Minutes range from 0 – 59.
The band limit can be changed by the
SET_WAIT
opcode.
GLDELAY
N/A
N/A
Delay Time