Page 65

background image

IDS 430/433 Users Manual Version 1.0

- 65 -

ISOLATED ANALOG OUTPUT OPTION IDS 430/433-AO

AN

ALOG OUTPUT OPTION

The Analog Output option board is internally mounted inside the IDS indicator. The Analog Output

has two jumpers, JP1 & JP2. These jumpers are used to configure the output format. Terminal

block TB1 is for making external wiring connections. JP1 & JP2 are factory set for 4-20mA. Refer

to the diagram below for configuration, format and alternative wiring. No interconnect cables are

provided by the factory, the recommended cables used should be suitable for the conduit fittings

and should comply with National Electrical code requirements.

INSTALLATION OF ANALOG OUTPUT BOARD

1. Before installation, remove power from the IDS indicator and remove the back plate to

access the internal board.

2. Refer to the PC Board Diagram to locate the installation connector and stand off holes on

the PC board.

3. Install the (2) plastic standoffs into the holes on the CPU board and plug the analog

output board (J1) onto the analog output connector. Secure the analog output module to

the CPU board by pushing the standoffs through the holes on the module.

4. Set JP1 and JP2 according to the desired output and connect the external device to TB1

according to the selected output.

5. Apply power to the IDS indicator and configure parameters 81, 82, and 83 as described

in the table below.

SETUP PARAMETERS

For proper operation, the following parameters are used to configure the operation of the analog

output.

Parameter

Description

Default

Value

81

Analog output span (20ma). The value entered here is the display graduations

(weight/count-by) and must correspond with the full-scale digits set in parameter 17.

If full scale capacity parameter 17= 10,000 then ( 0 lb’s = 4mA 10,000 lb’s = 20mA )

10,000

Must set to

a value

82

Analog output offset (4ma). The value entered here is the display graduations

(weight/count-by) and must correspond with the full-scale digits set in parameter 17.

0 (optional)

83

Analog output register/mode: 64 = Gross reg, 65 = Tare reg, 66 = Net reg

(Note: Scale Basic provides other registers (1-61,43-50, 64-68) which can be set based

on a mathematical formula) a register must be selected for the output to work

0 (must be

set to a reg

value)

Analog

Output
Connector

Stand off

hole

1 2 3

4

Ground

Voltage

Current

TB1

0- 5 VDC output

JP2/1

4-20 ma output

0-24mA output

0-20mA output

0-10 VDC option

U3

1

1

1 2 3 4

U6

U5

U4

J1 16 pin header

JP1

JP2

TB1

U2

1

Stand off

hole

10 VDC output

R4 option

R4

Optional

500ohm

0-10VDC

R4

This manual is related to the following products: