Specifications
72
Powerware
®
9 Prestige Series User’s Guide (4500/6000 VA)
S
Rev H
www.powerware.com
Electrical Specifications for the Prestige 6000 with PPDM
Use the following tables to determine load wiring requirements when
the PPDM is used with the UPS. The distribution of your load on the
available outputs of the PPDM may affect the maximum load obtainable.
Prestige 6000 PPDM Ratings with a Model 6000 UPS
PPDM Model
Input Utility Voltage
and Selected UPS
Output Voltage
Input
Current
Output Voltage and
Maximum Current
Maximum Output
Apparent Power**
208:120/208 Hardwired
220 Vac
(60 Hz only)
24A
127/220 Vac (60 Hz only),
30.0/25.0A
5500 VA
208:120/208 Hardwired
208 Vac
24A
120/208 Vac,
30.0/25.0A
5200 VA
208:120 L5-30R
208 Vac
24A
120 Vac,
43.3A*
5200 VA
208:120/208 L6-20R
208 Vac
24A
120/208 Vac,
15.0/20.0A
5200 VA
208:120/208 L6-30R
208 Vac
24A
120/208 Vac,
15.0/25.0A
5200 VA
208:120/240 L14-30R
208 Vac
24A
120/240 Vac,
15.0/21.1A
5000 VA
240:120/240 Hardwired
200 - 240 Vac
25A
100 - 120/200 - 240 Vac,
30.0/25.0A
6000 VA
240:120/240E Hardwired
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
30.0/25.0A
European IT Neutral
6000 VA
240:120 L5-30R
200 - 240 Vac
24A
100 - 120 Vac,
48.3A*
5800 VA
240:120/240 L6-20R
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
15.0/20.0A
5800 VA
240:120/240 L6-30R
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
15.0/24.7A
5800 VA
240:120/240 L14-30R
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
15.0/24.7A
5800 VA
*
**
*
Total of currents in all available 100 - 120V output connections.
*
**
**
**
*
Ratings based on 4000W load on PPDM, plus sufficient linear inductive load to achieve the current rating of the input
plug, not to exceed VA rating of PPU.
N
N
N
NO
O
O
OT
T
T
TE
E
E
E
Input and output currents are approximately the same when load is powered through bypass.