Installation
44
Powerware
®
9 Prestige Series User’s Guide (4500/6000 VA)
S
Rev H
www.powerware.com
9. Hardwire the input (TB1) and output terminations (TB2) for
the PPDM. See the following hardwired terminations table for
specifications. See Figure 17 for a detailed view of the terminal
blocks.
PPDM Hardwired Terminations
Wire Function
Terminal
Position
Terminal Wire
Size Rating
Suggested Wire
Size*
Conduit Connection
(Entry Size)
Input
L1
TB1-1
8 - 18 AWG
1 1/8
I (28 58 mm)
p
L2/Neutral
TB1-2
8 - 18 AWG
(10 - 0 mm
2
)
10 AWG
2
1 1/8
I (28.58 mm)
access hole for
Ground
TB1-3
10 - 18 AWG
(6 - 0 mm
2
)
(6 mm
2
)
3/4
I (19.05 mm)
conduit
Output
Model and Voltage
D
d
(
h
TB2-3
p
g
Dependent (see the
following Output
TB2-2
1 3/8
I (34.93 mm)
ollowing Output
Wiring Table)
TB2-1
6 - 18 AWG
(16 - 0 mm
2
)
8 AWG
(10 mm
2
)
/
(
)
access hole for
1
I (25 4 mm)
Neutral
TB2-4
(16 - 0 mm
2
)
(10 mm
2
)
1
I (25.4 mm)
conduit
Ground
TB2-5
*
**
*
Use 75
°C copper wire. Suggested wire size is based on Model 240: 120/240 hardwire full load ratings applied to NEC
Code Table 310-16.
PPDM Hardwired Models Output Wiring
Model 208:120/208
Model 240:120/240
Model 240:120/240E
Output Voltage
Terminal Position
Output Voltage
Terminal Position
Output Voltage
Terminal Position
120V
(50/60 Hz)
TB2-2 and TB2-4
and/or
100V, 110V,
TB2-2 and TB2-4
and/or
100V, 110V,
TB2 3 and TB2 4
127V
(60 Hz only)
and/or
TB2-3 and TB2-4
100V, 110V,
115V, or 120V
and/or
TB2-3 and TB2-4
100V, 110V,
115V, or 120V
TB2-3 and TB2-4
208V
(50/60 Hz)
TB2 1 and TB2 3
200V, 220V,
TB2 2 and TB2 3
200V, 220V,
TB2 1 and TB2 4
220V
(60 Hz only)
TB2-1 and TB2-3
200V, 220V,
230V, or 240V
TB2-2 and TB2-3
200V, 220V,
230V, or 240V
TB2-1 and TB2-4