Powerware 6000 User Manual
Page 41

Installation
33
Powerware
®
9 Prestige Series User’s Guide (4500/6000 VA)
S
Rev H
www.powerware.com
6. Hardwire the input (TB1-1 through TB1-3) and output
terminations (TB2) for the PPU. See the following hardwired
terminations table for specifications. See Figure 11 for a
detailed view of the terminal blocks.
PPU Hardwired Terminations
Wire Function
Terminal
Position
Terminal Wire
Size Rating
Suggested Wire
Size*
Conduit
Connection
(Entry Size)
Input
Ground
TB1-1
10 - 18 AWG
(6 - 0 mm
2
)
10 AWG
1 1/8
I (28.58 mm)
access hole for
L1
TB1-2
8 - 18 AWG
10 AWG
(6 mm
2
)
access hole for
3/4
I (19.05 mm)
L2/Neutral
TB1-3
8 - 18 AWG
(10 - 0 mm
2
)
(
)
/
(
)
conduit
Output
L1
TB2-1
8 - 18 AWG
1 1/8
I (28 58 mm)
p
L2/Neutral
TB2-2
8 - 18 AWG
(10 - 0 mm
2
)
10 AWG
2
1 1/8
I (28.58 mm)
access hole for
Ground
TB2-3
10 - 18 AWG
(6 - 0 mm
2
)
(6 mm
2
)
3/4
I (19.05 mm)
conduit
REPO
L1
TB1-4
7/8
I (22.23 mm)
L2
TB1-5
12 - 22 AWG
(4 - 0 mm
2
)
18 AWG
(0 75 mm
2
)
/
(
)
knock-out for
1/2
I (12 70 mm)
Ground
TB1-6
(4 - 0 mm
2
)
(0.75 mm
2
)
1/2
I (12.70 mm)
conduit
*
**
*
Use 75
°C copper wire. Suggested wire size is based on Model 6000 full load ratings applied to NEC Code Table 310-16.