Powerware 6000 User Manual
Page 44

Installation
36
Powerware
®
9 Prestige Series User’s Guide (4500/6000 VA)
S
Rev H
www.powerware.com
UPS Startup
To start up the UPS:
1. Verify the input breaker on the PPU rear panel is in the
OFF (O) position (see Figure 4 on page 26).
2. Confirm the correct UPS output voltage is selected (see Step 7
on page 27).
3. Turn on the equipment that is connected to the UPS.
4. If your PPU is a hardwired unit, supply utility power to the UPS
and skip to Step 7.
5. If your PPU is a plug/receptacle unit, plug the UPS power
supply cord into the power input connector on the PPU rear
panel.
6. Plug the other end of the power supply cord into a grounded,
three-wire, AC receptacle that has been wired in accordance
with NEC specifications or national wiring rules. See Chapter 6,
“Specifications” on page 69 for the input current/output voltage
requirements.
7. Switch the circuit breaker to the ON (
|
) position (see Figure 4
on page 26) on each battery cabinet connected to the PPU.
Each battery cabinet performs a self-test and then enters normal
operation. The battery cabinet startup should take about three
seconds.
8. Switch the PPU input breaker to the ON (
|
) position (see
Figure 4 on page 26).
The UPS performs diagnostic tests and enters Normal mode
with the equipment (load) offline. The
µ
indicator remains
lit. The startup should take about 15 seconds.
9. Press and hold the Output On button until you hear the UPS
beep (approximately one second).