Installation, Warning, Do not install in sleeping room – Harman Stove Company HARMAN P68 User Manual
Page 6
6
P68 Pellet Stove
3-90-00688R24_06/13
installing
Place the stove on a noncombustible type floor or floor protector
that extends a minimum of 6 inches (152mm) to the front of the
load door opening, 6 inches (152mm) to the sides of the door
opening, and 6 inches to the rear. Floor protection must also
extend 2 inches (51mm) beyond each side of any horizontal flue
pipe. The minimum floor protector material is 20 gauge sheet
metal. Other floor protector materials are ceramic tile, stone,
brick, etc.
note for canadian installation only: Per ULC-S627-00,
If installed on a combustible floor, the need to provide a
noncombustible floor protector covering the area beneath the
space heater and extending at least 17.72" (450mm) on the firing
side and at least 7.87" (200mm) on the other sides.
In Canada, you may follow smaller U.S. floor protection
requirements onlY if the user agrees to completely shut-
down the appliance, and allow it to cool to where all fire is
extinguished and the combustion blower and its indicator
light shuts off, prior to opening the firebox door or ash door.
Place the stove away from combustible walls at least as far as
shown in Figures 3 and 4. Please note the difference in side wall
clearance with and without side shields.
Note that the clearances shown are minimum for safety but do not
leave much room for access when cleaning or servicing. Please
take this into account when placing the stove.
Connect the power cord to a 120 V.A.C. 60Hz grounded
receptacle. (A surge protector is recommended to protect the
circuit board.) Also be sure that the polarity of the outlet that the
stove is plugged into is correct.
Prior to installing the flue pipe, connect a draft meter. (The
draft meter must have a minimum range of 0 - .5") Record the
first reading. Connect flue pipe to stove and be sure all doors
and windows in the home are closed. Record the second draft
reading_______. If the second reading is more than .05" lower
than the first reading, check for possible restrictions or the need
for outside air (see page 10). For more information on the draft
test procedure, refer to Page 21.
Mobile home installation
When installing this unit in a mobile home, several requirements
must be followed:
1. The unit must be bolted to the floor. This can be done with 1/4"
lag screws through the 2 holes in the base plate.
2. The unit must also be connected to outside air. See page 10.
3. Floor protection and clearances must be followed as shown.
4. Unit must be grounded to the metal frame of the mobile home.
5. Be sure to follow the vent manufacturer's guidelines to provide
for a sufficient vapor barrier where the flue penetrates the
outside.
6. The top section of any chimney or venting must be removable
to a height of 13' (3.9 M) to allow for transport.
7. The factory-built chimney must conform to CAN/ULC-S629,
Standard for 650°C Factory-Built Chimneys.
caution: this appliance must be vented to the outside.
Clothing and other flammable materials should not be placed on
or near this unit.
installation
l
j
Floor Protection
requirements
US
Canada
Sides
Rear
6"
200mm
6"
200mm
K
Front
6"
450mm
Fig. 3
9"(228mm)With Side Shields
13"(330mm) Without Side Shields
Fig. 4
2"(51mm)
36"(914mm)
14" (355mm) with
side shields
20" (508mm)
without side shields
14" (355mm)
20" (508mm)
Minimum size rectangular floor protection (USA) is
28
5/16
" Deep By 24
3/4
" Wide.
* Floor protection dimensions for the front and sides
are measured from the appliance door opening in
The United States. In Canada, the side dimension is
measured from the widest part of the appliance.
j
usa
K
l
j
canada
note:
Measurement "L"
is measured from
the pedestal base
in the US ONLY
note:
Measurement "K"
is measured from
the glass in the
US ONLY
F
loor
protector
the structural integritY oF the
ManuFactured hoMe Floor, Wall, and
ceiling/rooF Must be Maintained.
Warning
do not install in sleePing rooM.
9"(228mm)-
13"(330mm)
9"(228mm)-
13"(330mm)
Alternate floor protector
dimension may be used
as long as they satisfy the
measurement requirements
shown below.
Minumum size floor protection
for a corner installation is 36"
x 36". Clearance shown as
9" with optional side shields
installed.