P68 Pellet Stove

3-90-00688R24_06/13

installing

Place the stove on a noncombustible type floor or floor protector

that extends a minimum of 6 inches (152mm) to the front of the

load door opening, 6 inches (152mm) to the sides of the door

opening, and 6 inches to the rear. Floor protection must also

extend 2 inches (51mm) beyond each side of any horizontal flue

pipe. The minimum floor protector material is 20 gauge sheet

metal. Other floor protector materials are ceramic tile, stone,

brick, etc.

note for canadian installation only: Per ULC-S627-00,

If installed on a combustible floor, the need to provide a

noncombustible floor protector covering the area beneath the

space heater and extending at least 17.72" (450mm) on the firing

side and at least 7.87" (200mm) on the other sides.

In Canada, you may follow smaller U.S. floor protection

requirements onlY if the user agrees to completely shut-

down the appliance, and allow it to cool to where all fire is

extinguished and the combustion blower and its indicator

light shuts off, prior to opening the firebox door or ash door.

Place the stove away from combustible walls at least as far as

shown in Figures 3 and 4. Please note the difference in side wall

clearance with and without side shields.

Note that the clearances shown are minimum for safety but do not

leave much room for access when cleaning or servicing. Please

take this into account when placing the stove.

Connect the power cord to a 120 V.A.C. 60Hz grounded

receptacle. (A surge protector is recommended to protect the

circuit board.) Also be sure that the polarity of the outlet that the

stove is plugged into is correct.

Prior to installing the flue pipe, connect a draft meter. (The

draft meter must have a minimum range of 0 - .5") Record the

first reading. Connect flue pipe to stove and be sure all doors

and windows in the home are closed. Record the second draft

reading_______. If the second reading is more than .05" lower

than the first reading, check for possible restrictions or the need

for outside air (see page 10). For more information on the draft

test procedure, refer to Page 21.

Mobile home installation

When installing this unit in a mobile home, several requirements

must be followed:

1. The unit must be bolted to the floor. This can be done with 1/4"

lag screws through the 2 holes in the base plate.

2. The unit must also be connected to outside air. See page 10.

3. Floor protection and clearances must be followed as shown.

4. Unit must be grounded to the metal frame of the mobile home.

5. Be sure to follow the vent manufacturer's guidelines to provide

for a sufficient vapor barrier where the flue penetrates the

outside.

6. The top section of any chimney or venting must be removable

to a height of 13' (3.9 M) to allow for transport.

7. The factory-built chimney must conform to CAN/ULC-S629,

Standard for 650°C Factory-Built Chimneys.

caution: this appliance must be vented to the outside.

Clothing and other flammable materials should not be placed on

or near this unit.

installation

l

j

Floor Protection

requirements

US

Canada

Sides

Rear

6"

200mm

6"

200mm

K

Front

6"

450mm

Fig. 3

9"(228mm)With Side Shields

13"(330mm) Without Side Shields

Fig. 4

2"(51mm)

36"(914mm)

14" (355mm) with
side shields

20" (508mm)
without side shields

14" (355mm)

20" (508mm)

Minimum size rectangular floor protection (USA) is

28

5/16

" Deep By 24

3/4

" Wide.

* Floor protection dimensions for the front and sides

are measured from the appliance door opening in

The United States. In Canada, the side dimension is

measured from the widest part of the appliance.

j

usa

K

l

j

canada

note:

Measurement "L"

is measured from

the pedestal base

in the US ONLY

note:

Measurement "K"

is measured from

the glass in the

US ONLY

F

loor

protector

the structural integritY oF the

ManuFactured hoMe Floor, Wall, and

ceiling/rooF Must be Maintained.

Warning

do not install in sleePing rooM.

9"(228mm)-

13"(330mm)

9"(228mm)-

13"(330mm)

Alternate floor protector

dimension may be used

as long as they satisfy the

measurement requirements

shown below.

Minumum size floor protection

for a corner installation is 36"

x 36". Clearance shown as

9" with optional side shields

installed.