Condition

Possible cause

Checks

Action

Engine stops without
having to press STOP
button or before run
time is complete

Water and Fuel
solenoid circuits and
valves, or

Main Logic Board
faulty

Check Water and Fuel
Relay

Replace Engine Relay
Board

Replace Main Logic
Board

Test Timer or Test
Pushbutton does not
start engine
AUTOMATIC /
MANUAL SWITCH in
AUTO

Engine starts after
pressure drop

No power to solenoid
drain valve, or faulty
valve

Faulty Timer

Check Water Dump
Solenoid Relay

Check solenoid valve

Check Timer
program

Replace Engine Relay
Board

Replace valve

Replace Timer

Alarm does not sound,
Associated light not on

Alarm faulty

LED Display faulty

Main Logic Board
faulty

Check alarm

Replace alarm

Replace LED Display

Replace Main Logic
Board

No BATTERY
FAILURE indication

Engine cranks

Power Sense Board
faulty

Main Logic Board
faulty

Check Power Sense
Board

Replace Power Sense
Board

Replace Main Logic
Board

Table 6-1 Troubleshooting (Continued)