High water temperature test, Optional remote start, Optional ac power failure start (if enabled) – Hubbell Diesel Engine Fire Pump Controller LX3000 User Manual

Page 5

background image

b. Wait 10 seconds for the Oil Pressure Delay interval to expire, then momentarily jumper TB1-4 to TB1-11.

The alarm will sound and the Common Trouble relay will energize. The LOW OIL PRESSURE LED will
come on and remain on after the engine stops.

c. Turn the CONTROLLLER ON / OFF - RESET SWITCH to the OFF - RESET position then back to the

CONTROLLER ON position to reset the LOW OIL PRESSURE Alarm.

High Water Temperature Test

a. WITH the AUTOMATIC / MANUAL SWITCH in the AUTOMATIC position, start the engine by

depressing the TEST PUSHBUTTON on the Weekly Timer.

b. Momentarily jumper the TB1-5 to TB1-11. The alarm will sound and the Common Trouble relay will

energized. The HIGH WATER TEMPERATURE LED will come on and remain on after the engine stops.

c. Turn the CONTROLLLER ON / OFF - RESET SWITCH to the OFF - RESET position then back to the

CONTROLLER ON position to reset the HIGH WATER TEMPERATURE Alarm.

Optional Remote Start

a. With the

AUTOMATIC / MANUAL SWITCH

in the

AUTO

position, open the remote start contacts, TB1-12

& 13, starting the engine.

b. Turn the CONTROLLER ON / OFF SWITCH to the OFF position to stop engine.

c. Close the remote start contacts.

Optional AC Power Failure Start (if enabled)

a. With the

AUTOMATIC / MANUAL SWITCH

to the

AUTO

position, disconnect the AC power supply to the

Controller.

b. After the pre-set time delay (0 to 90 seconds) the engine will start. The audible alarm should sound,

AC

POWER LOSS

LED will come on, and both the Common

TROUBLE

and

AC POWER LOSS

relays will

energize.

c. Reconnect the AC power to reset the alarms.

d. Turn the

CONTROLLER ON / OFF - RESET SWITCH

to the

OFF - RESET

position to stop the engine.

End of Startup Testing

Switches

1. Automatic/Manual – Selects automatic or manual mode.

2. Crank Battery 1 – Cranks the engine using battery 1.

3. Crank Battery 2 – Cranks the engine using battery 2.

4. Stop – Stops the engine in automatic if there are no start conditions and control switch is in “Auto”.

5. Normal/ Silence – Silences optional pump house alarm only. Standard alarms required NFPA 20 cannot be

silenced.