beautypg.com

Hubbell Diesel Engine Fire Pump Controller LX3000 User Manual

Page 10

background image

No HIGH ENGINE
TEMP indication

Water temperature
switch

Connect a jumper
across the water
temperature switch on
the engine
Start engine with
MANUAL START
switch
Verify that engine starts
and alarm sounds

Replace water
temperature switch

Engine overspeed does
not stop engine
No indication

Indication but engine
does not stop under
overspeed simulation

Faulty or mis-adjusted
magnetic sensor

Main Logic Board
faulty

Check sensor
installation

Replace sensor

Replace Main Logic
Board

Cranking and rest
periods greater than or
less than 15

± 2 sec.

Engine cranks less than
six times

Engine continues to
crank in AUTO
position but does not
start

Main Logic Board
faulty

Check Main Logic
Board

Replace Main Logic
Board

Controller does not
crank engine with good
battery

Engine cranking and
indication OK

Engine Relay Board
faulty

Main Logic Board
faulty

Check Engine Relay
Board

Check Main Logic
Board

Replace Engine Relay
Board

Replace Main Logic
Board