Table 6-1 Troubleshooting (Continued)

Condition

Possible cause

Checks

Action

Engine does not crank
with Remote Start

Cranks when water
pressure decreases

Remote switch faulty

Main Logic Board
faulty

Check switch and
switch circuits

Check Main Logic
Board

Repair circuits
Replace switch

Replace Main logic
Board

Engine does not start
after AC power loss

Power Sense Board or
Main Logic Board
faulty

Check Power Sense
Board

Check Main Logic
Board

Replace Power Sense
Board

Replace Main Logic
Board

Engine does not stop
with optional AUTO
STOP

Another start condition
present

Main Logic Board
faulty

Check controller start
conditions

Check Main Logic
Board

Replace Main Logic
Board

Note

The above troubleshooting guide does not represent all possible conditions or problems. If the above
information can not resolve a problem, consult the factory or a local representative for further assistance.