beautypg.com

Hubbell 4310 User Manual

Fused magnet safety disconnect switch 4310

background image

Hubbell Industrial Controls, Inc.

Fused Magnet Safety Disconnect Switch

4310

Catalog 4310 • August 2003 • New

Hubbell Industrial Controls, Inc.

A subsidiary of Hubbell Incorporated

4301 Cheyenne Dr., Archdale, NC. 27262

Telephone (336) 434-2800 • FAX (336) 434-2803

http://www.hubbell-icd.com

[email protected]

Description

The 4310 fused magnet safety disconnect switch is
designed to safely allow the operator of a lifting magnet
to disconnect the highly inductive magnet while the
magnet is still energized. Standard safety switches are
not designed to safely disconnect an energized magnet.

The 4310 has (3) power poles. Two normally open
power poles to disconnect the incoming power and a
third normally closed power pole that shunts the
magnets energy into a discharge resistor when the
disconnect is switched to the off position.

Features

• Supplied in a NEMA type 3R wall mounting

enclosure.

• Rated 300 VDC. Max
• All switches have a padlockable thru-the-door

operator

• High capacity discharge resistor

Enclosure Dimensions

Part Number

Fused At

Magnet Amps (Max)

H

W

D

List Price E43

4310-86262-004

100 Amps

67

29.00

12.63

10.00

$1,900.00

4310-86262-002

200 Amps

134

29.00

12.63

10.00

$2,250.00

4310-86273-001

400 Amps

267

31.25

24.00

13.29

$6,130.00

How To Order

Specify magnet operating current, cold.

Enclosure type is NEMA 3R

Order by part number