Hubbell Electric Fire Pump Controllers LXi 2800 User Manual
Hubbell Computer Accessories
Hubbell Industrial Controls, Inc.
Electric Fire Pump Controllers
Specifications for
LXi
2800 Controllers * Wye-Delta Closed Transition Starting With Transfer Switch * July 2002
The fire pump controller shall be factory assembled, wired, and tested as a unit assembly, shall conform to the requirements of the latest
editions of NFPA-20 and NFPA-70, and shall be Listed/Approved by and bear the label of UL/FM. The controller shall be Hubbell-
Lexington
LXi
2800 equipped with
LXi
logic.
The controller shall be of the combined manual/automatic type and be furnished in a floor mounted drip-proof steel Type 2 enclosure with
lifting eyes. The enclosure shall be red with a non-glare surface. The controller shall be for wye-delta closed transition starting and
designed, tested, and marked for the rated horsepower and 3-phase voltage and frequency in a 40 degree C. ambient.
All electrical components shall be accessible from the front for maintenance and service. No components or component wiring shall be
permitted on the door of the enclosure. The controller shall have a common operating handle for both the line isolating switch and the
controller circuit breaker mounted in the enclosure flange. The minimum withstand rating for the fire pump controller shall be 150,000
amps RMS symmetrical at 200-600volts. The unit shall be Listed/Approved with UL/FM as “Suitable For Use As Service Equipment”.
The controller shall have separate and independent pressure settings with minimum run timing capable of a setting of 10 minutes.
Settings of the pressures shall be established at the time of the field acceptance test. Provisions shall be included to allow manual or
automatic shut-down in the field.
The controller shall have two sets of Form “C” contacts for Pump Running, Phase Reversal, Power/Phase Failure, and one set of Form
“C” contacts for Trouble. The Trouble contacts shall be activated by the following conditions: Invalid Configuration Memory,
Emergency Manual Start, Pump Running, Phase Failure, Phase Reversal, Overload, Locked Rotor, Fail-to-Start, and Lockout.
The controller shall be equipped with
LXi
intelligent fire pump control system logic. All firmware shall be non-volatile flash based CPLD
( complex-programmable logic device). The boot-up time for the logic shall be 3 seconds or less. Controllers that do not boot-up and
allow the pump to be started in 3 seconds or less are not acceptable. An RS232 serial port shall be supplied for downloading event history
to a PC for analysis and printing.
The digital pressure readings and settings shall be displayed on the
LXi
LCD mounted on the enclosure flange. The LCD screen shall be 4
x 20 (4 lines of 20 characters) per screen, and the screens may be scrolled to give a total of 320 characters. The real time display shall give
simultaneous 3-phase digital amps and volts for the pump power, and digital display for the system pressure. Controllers that do not
simultaneously display digital 3-phase amps, line-to-line volt readings, and system pressure, are not acceptable.
The event alarm caches shall be compartmentalized, and no compartment shall over-ride any other compartment. The compartments
allow for analysis of four types of information events without having to look through all events including those not related to a problem.
Events shall be shown with Date and Time for each event occurrence:
1. Events that have occurred during a pump idle period
2. Events that occurred during the last start period
3. Events that occurred during the last run period
4. Events that occurred during the last stop period.
The LED displays shall be mounted on the enclosure flange and have an LED for the following, with provisions for three spare LED’s to
be available and programmable for other options or event displays.
Power Available
Fail to Start
Lockout On
Low Suction
Phase Reversal
Run Timer On
Pump Start Delay On
Shorted SCR
Pump Running
Locked Rotor
Overload
Overtemp SCR
Pressure Switch Start
Local Manual Start
Remote Start
Emergency Manual Start
Local Manual Stop
Start Timer/Accelerate
The LED displays shall be mounted on the enclosure flange and have an LED for the following:
Programming of the
LXi
logic shall be from the touch pad mounted on the enclosure flange. Programming shall be password protected so
that only authorized personnel can change the logic functions. The fire pump controller shall be Model
LXi
2800 equipped with
LX
i Logic
as manufactured by Hubbell Industrial Controls, Inc.