Venting, 4 installing into an existing chimney, 5 installing into an existing fireplace chimney – Harman Stove Company Harman Pellet P43 User Manual

Page 12

background image

12

P43 Pellet Stove

3-90-04301R18_03/13

#4 installing into an existing chimney

This method provides excellent venting for normal

operation. This method also provides natural draft in

the event of a power failure. If the chimney condition

is questionable* you may want to install a liner as in

method #7.

In some places in the US and Canada it is required

that the vent pipe extend all the way to the top of the

chimney.

*The chimney should be inspected and cleaned before

installing your stove. If you discover that the chimney

does not have a clay tile liner or has cracks or flaking of

the tile liner you will need to install a stainless steel liner

within the chimney. In most cases the inside diameter

of this liner should be 4". Either flexible or rigid liner

may be used for this purpose. Refer to Method 6 & 7.

Be sure to design the venting so that it can be easily

cleaned.

#5 Installing into an existing fireplace

chimney

This method provides excellent venting for normal

operation. This method also provides natural draft in

the event of a power failure. If the chimney condition

is questionable* you may want to install a liner as in

method #6.

In some places in the US and Canada it is required

that the vent pipe extend all the way to the top of the

chimney.

*The chimney should be inspected and cleaned before

installing your stove. If you discover that the chimney

does not have a clay tile liner or has cracks or flaking of

the tile liner you will need to install a stainless steel liner

within the chimney. In most cases the inside diameter

of this liner should be 4". Either flexible or rigid liner

may be used for this purpose. Refer to Method 6 & 7.

The chimney should be sealed at the damper using a

steel plate. Kaowool, mineral wool or an equivalent non-

combustible insulation is recommended to be installed

on top of the sealing plate to reduce the possibility

of condensation. The connector pipe should extend

through the smoke chamber to the base or into the

first flue tile.

Be sure to design the venting so that it can be easily

cleaned.

Fig. 10

Fig. 11

venting