Configuration parameters, Configuration parameters -2 – HP T2200 XR User Manual

Page 25

background image

Configuration

3-2

HP Uninterruptible Power System T2200 XR Models User Guide

2. Press and hold the Configure button (2) for three seconds. When the Configure button is

released, the front panel configuration parameters flash in unison and the Configure
Mode On LED (1) illuminates solid green.

1

2

Figure 3-2: Placing the UPS in Configure mode

Configuration Parameters

In Configure mode, the front panel LED display changes function to allow UPS monitoring.
The LED control buttons allow modification of the UPS configuration parameters. The
configuration parameters are defined in Table 3-1. Available voltage settings per model are
listed in Table 3-2.

Table 3-1: Configuration Parameters

Parameter (LED)

Parameter Name

Explanation (when illuminated)

General Alarm

(

)

100/200-208

Nom

Nominal utility voltage level is selected to 100/208 VAC.

On Battery

(

)

110/220 Nom

Nominal utility voltage level is selected to 110/220 VAC.

Bad Battery/Low

Battery

(

)

120/230 Nom

Nominal utility voltage level is selected to 120/230 VAC.

Site Wiring Fault

Indicator

(

)

127/240 Nom

Nominal utility voltage level is selected to 127/240 VAC.

Utility LED

(

)

Site Wiring

Fault Indicator

Audible alarm is enabled if ground is missing, or if line
and neutral connections are reversed.