Modes of operation, Modes of operation -2 – HP T2200 XR User Manual

Page 19

background image

Operation

2-2

HP Uninterruptible Power System T2200 XR Models User Guide

continued

Item Description

Meaning/Function

6

Site Wiring Fault
Indicator (

)

Red—No ground connection exists between utility power and the UPS,
the line and neutral connections between utility power and the UPS
are reversed, or the UPS voltage configuration is incorrect.

7

Utility LED (

)

Flashing Red—Utility input voltage is outside the +20% to -30%
configured nominal range.

Green—Utility voltage is present and output is on, or utility voltage has
returned to the voltage range for which the UPS has been configured
(UPS is supplying utility power and the audible alarm should be reset).

Flashing Green—Utility voltage is present and the UPS is in Standby
mode. Output is off. Batteries charge if needed.

8 Bad

Battery/Low

Battery (

)

Red—Battery is bad or low.

9

On Battery (

)

Red—UPS is running on battery power.

10

General Alarm (

)

Red—UPS detects a general alarm. Perform a self-test.

11

Configure Mode On
LED

Green—UPS is in Configure mode (seen when front bezel removed).

12 Configure

button

Places the UPS in Configure mode (seen when front bezel removed).

13 Test/Alarm

Reset

button

Resets alarms or initiates self-tests.

14

Standby button

Places the UPS in Standby mode (turns output load segments off).

15 On button

Starts UPS powering the load.

Modes of Operation

The UPS has three modes of operation:

Standby Mode

— No power is available at the UPS output receptacles.

— The UPS charges the batteries as necessary.

Operate Mode

— Power is available at the UPS output receptacles.

— The UPS charges the batteries as necessary.

Configure Mode

— Power is available at the UPS output receptacles.

— The UPS charges the batteries as necessary.

— The UPS configuration can be updated.