2 event schedule setup and examples – Honeywell SERIES COMMUNICATING TB7600 User Manual
Page 11

TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS
11
62-2016—01
Table 7. Permanent Temperature Setpoint Changes User Menu Sequence
SYSTEM MODE SETTING
This menu is accessed to set system mode operation. Use to set value, Yes key to confirm.
• Sys mode auto: Automatic changeover mode between heating and cooling operation
• Sys mode cooling: Cooling operation mode only
• Sys mode heating: Heating operation mode only
• Sys mode emergency: (Heat pump models only) Forced auxiliary heat operation mode only
• Sys mode off: Normal cooling or heating operation disabled. If enabled in installer parameters, only the automatic
heating frost protection at 50 F (10 C) is enabled
FAN MODE SETTING
This section of the menu is permits the setting of the fan mode operation. Use to set value,
Yes key to confirm
• Fan mode On: Fan is on continuously, even when system mode is OFF.
• Fan mode Auto: Fan cycles on a call for heating or cooling for both occupied and unoccupied periods.
• Fan mode Smart: During occupied periods, fan is on continuously. In unoccupied mode, fan cycles on a call for
heating or cooling. This selection is available on all models.
SCHEDULE SET (2 OR 4 EVENTS)
The scheduling option at the thermostat can only be used if the thermostat is not connected to
the WEBs-AX building control network. Once the thermostat is connected to the network, all
scheduling should be done through the WEBs-AX Workbench/Supervisor. Schedules set
through the network cannot be viewed on the thermostat. Thermostats with local scheduling can
have 2 or 4 events per day. Whether 2 or 4 events per day are allowed is set in the configuration
parameter 2/4 event.
If set for 2 events, the user can set two events per day, establishing occupied and unoccupied times. If set for 4 events,
the user can set four events per day, establishing occupied and unoccupied times. Each day can be tailored to specific
schedules if needed.
NOTE: 12:00 PM = Noon
2 Event Schedule Setup and Examples
Table 8. Set 2 Events Per Day Menu Navigation
Cooling setpoint
Occupied mode
Heating setpoint
Occupied mode
Cooling setpoint
Unoccupied mode
Heating setpoint
Unoccupied mode
°F or °C
display setting
Cooling
set?Y/N
No next
→
Yes down
↓
Heating
set?Y/N
No next
→
Yes down
↓
Unocc CL
set? Y/N
No next
→
Yes down
↓
Unocc HT
set? Y/N
No next
→
Yes down
↓
F or C
set?Y/N
No next
→
Yes down
↓
Use to set value, Yes key to confirm
Cooling
70.0°F
Use
To set value
Heating
68.00°F
Use
To set value
Unocc CL
80.0°F
Use
To set value
Unocc HT
60.0°F
Use
To set value
Units
°F
Use
To set value
Monday timer
Schedule set
Tuesday timer
Schedule set
Wednesday timer
Schedule set
Other days are identical
Monday
set?Y/N
No next
→
Yes down
↓
Tuesday
set? Y/N
No next
→
Yes down
↓
Wednesda
set? Y/N
No next
→
Yes down
↓
Selects the day to be programmed or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next
→
Yes down
↓
Occupied
Day? Y/N
No next
→
Yes down
↓
Occupied
Day? Y/N
No next
→
Yes down
↓
Yes = Daily schedules will be accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next
→
No down
↓
Copy Y/N
Previous
Yes next
→
No down
↓
Yes = Will copy previous day schedule
No = Daily schedules will be accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use
To set value
Occupied
00:00 AM
Use
To set value
Occupied
00:00 AM
Use
To set value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use to set value, Yes key to confirm
Unoccup
00:00 AM
Use
To set value
Unoccup
00:00 AM
Use
To set value
Unoccup
00:00 AM
Use
To set value
Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints
Use to set value, Yes key to confirm
M16940
M16941
M16942
62-2016.fm Page 11 Thursday, April 14, 2011 1:40 PM