6 analog output configuration, 1 identifying the output type, 2 channel menu items – Honeywell SC1000 User Manual
Page 76: 3 output selection

page 76 008-0608-00
10.6 Analog Output Configuration
10.6.1 Identifying the
Output Type
A Strain-Gage Input channel is available with one of two types of digital-to-analog
(DAC) outputs: voltage or current. You can determine which type of output a
channel has by one of three ways:
•
Consulting the instrument’s Customer Information Sheet
•
Examining the
SYSTEM MENU
->
CONFIGURATION
->
CHANNEL
nn
TYPE
menu item where
nn is the number of the channel. If the channel’s type is
STRAIN GAGE V
, it has a
voltage output. If the channel’s type is
STRAIN GAGE I
, it has a current output.
•
Examining the channel’s circuit board as shown in the figure below.
10.6.2 Channel Menu Items
The Analog Output can be driven by any channel’s track, peak or valley value.
See the “Channel Menu” section earlier in this chapter for a complete listing of
SETUP menu items available on the
DAC. SETUP
sub-menu.
10.6.3 Output Selection
Jumpers located on the channel’s circuit board determine what outputs are gener-
ated when the value selected to drive the Analog Output (from the
DAC. CHANNEL
and
DAC. SOURCE
menu items) equals the
DAC. FULL SCALE
and
DAC. ZERO SCALE
settings.
Figure 10-3: Digital-to-Analog Output Jumper Locations
DAC. ZERO SCALE
Output
DAC. FULL SCALE
Output
J30
jumper
J31
jumper
CHANNELS WITH VOLTAGE OUPUT
0-5V
2.5 Volts
5 Volts
open
closed
±5V
0 Volts
5 Volts
open
open
0-10V
5 Volts
10 Volts
closed
closed
±10V
0 Volts
10 Volts
closed
open
CHANNELS WITH CURRENT OUTPUT
4-20mA
4 mA
20 mA
open
open
4-20mA
12 mA
20 mA
open
closed