beautypg.com

4 calibration type menu item – Honeywell SC1000 User Manual

Page 113

background image

SC Series Instruction Manual page 113

Hig

h-L

ev

el

In

pu

t C

han

nel

12

12.6.4

CALIBRATION TYPE

Menu Item

This chooses the type of calibration technique to be used. There are two methods
that can be used to calibrate the transducer to the Input Channel. Each has
advantages and disadvantages as described in the table below.

It is important to know your application in order to select the appropriate cali-
bration type. When the best possible accuracy is required, Known-Load Calibra-
tion is recommended. However, if known-loads are not available, Shunt
Calibration may be used instead.

The choices for this menu item are:

TYPE= SHUNT CAL

” means Shunt Calibration. First, you are prompted to apply

the load entered in the “

ZERO SCALE VALUE

” register. Next, the instrument inter-

connects the Shunt Cal 1 and Shunt Cal 2 pins. This activates the trans-
ducer’s or in-line amplifier’s shunt calibration circuit which causes a
predictable apparent signal. The instrument then takes a reading and adjusts
itself using the “

SHUNT CAL VALUE

” register.

TYPE= 2 POINT CAL

” means 2-Point Known Load Calibration. You are prompted

to apply the loads to the transducer that were entered in the “

KNOWN POINT 1/2

and “

KNOWN POINT 2/2

” registers. This technique assumes that the transducer is

linear, so the usual loads used are zero scale and full scale.

TYPE= 3 POINT CAL

” means 3-Point Known Load Calibration. You are prompted

to apply the loads to the transducer that were entered in the “

KNOWN POINT 1/3

and “

KNOWN POINT 2/3

” and “

KNOWN POINT 3/3

” registers. This technique can be

Table 1-7: Comparison of Calibration Types

Shunt Calibration

2-, 3-, or 5-point

Known Load

Calibration

RECOMMENDED...

...for most applications

no

yes

...when frequently swapping

transducers

yes

no

...when best possible accuracy

required

no

yes

PROS and CONS

Relative accuracy

good

best

Requires actual, calibrated loads

to be applied

no

yes

CALIBRATION TECHNIQUE

Zero-scale point from...

applied load

applied load

Full-scale point from...

transducer output

when Shunt Cal pins

connected

applied load

Linearity correction from...

N/A

2-point: none

3- or 5-point:

applied load

This manual is related to the following products: