beautypg.com

Output specifications, Overcurrent protection – HP R12000 XR User Manual

Page 64

background image

Specifications

Output Specifications

Table C-3: Output Specifications

UPS Model

Effective VA

Nominal Power Rating
(W)

R12000 XR WW
(worldwide)

12000 12000

Characteristics

Configuration
Setting (VAC)

Available Nominal
Output Voltage (VAC)

Voltage

The input voltage
range is 200-240 VAC
±20%.

200, 208, 220, 230 or 240

Source of Power

Regulation

Output Utility

power

(normal range)

±3% of nominal output
voltage rating (within the
guidelines of the Computer
Business Equipment
Manufacturers Association)

Battery

power

±3% of nominal output
voltage rating

Feature

Specification

Other features

Online efficiency

> 83%

Voltage wave shape

Sine wave; 3% THD with
typical PFC load

Surge suppression

High energy 6500 A peak

Noise filtering

The input noise
suppression is comprised
of Normal Mode Filtering,
Common Mode Filtering, or
a combination of both.

Overcurrent Protection

A power distribution unit (PDU) provides overcurrent protection.

C-2

HP Uninterruptible Power System R12000 XR Models User Guide