beautypg.com

Modes of operation, Modes of operation -4 – HP R12000 XR User Manual

Page 20

background image

Operation

Modes of Operation

The UPS has five modes of operation, indicated by the LEDs (see Figure 2-3):

Standby Mode

— When utility is present and output is off, the Utility LED (1) flashes slowly.

— Power is not available at the UPS output.

— The UPS monitors and charges batteries, if required.

Operate Mode

— The Utility LED (1) is solid green.

— The UPS is supplying power to the loads.

— The UPS monitors and charges batteries, if required.

Bypass Mode

— The Utility LED (1) and Battery LED (2) are off.

— The Bypass LED (3) is solid amber, and an audible alarm is active.

— The Alarm LED (4) is solid red.

— The utility is bypassing the unit and going directly to the load.

— The UPS monitors and charges batteries, if required.

Battery Mode

— The Battery LED (2) is solid amber.

— The Alarm LED (4) is solid red.

— Utility power is not present.

— The UPS does not charge the batteries.

— Power is available at UPS outputs.

Redundant Mode

— The Redundant LED (5) is solid green.

— At least one electronics module of the load can be in a redundant state (two or more

electronics modules working).

— All electronics modules share the load, but there is enough power to allow an

electronics module to go out of service.

2-4

HP Uninterruptible Power System R12000 XR Models User Guide

HP CONFIDENTIAL Codename: Sierra Part Number: 146316-002 Last Saved On: 1/24/03 10:14 AM