LCD Configuration and Status

Matching the Utility Voltage

Use configuration parameters to select the UPS voltage range (see Table 3-1).

If the utility voltage is within this range, the UPS supplies utility power to the output
receptacles.

If the utility voltage is outside this range, the UPS supplies battery power to the output
receptacles.

If the utility voltage frequently varies outside the operating range, update the UPS
configuration to match.

NOTE: When you set the voltage through the LCD panel (as described in the “Setting the Voltage”
section of this chapter), you are setting the UPS output voltage

Table 3-1: Voltage Ranges (VAC)

Nominal Utility
Voltage Level

Normal Utility
Voltage Range

UPS Output
Voltage

200 166-240

200

208 166-248

208

220 176-264

220

230 (default)

184-276

230

240 192-288

240

To update the configuration:

1. Have a licensed electrician measure your utility voltage.

2. Use Table 3-1 to identify the operating range that most closely matches your nominal

utility voltage level.

3. Update the UPS output voltage as required. Refer to the section, “Setting the Voltage,” in

this chapter for more information.