beautypg.com

A.6.1 setup inputs, A.6.2 setup common alarm, A.6.1 – Emerson Autochangeover Controllers AC8 User Manual

Page 105: Setup inputs, A.6.2, Setup common alarm, Section a.6.1, Section a.6.2

background image

Setup Menu

97

A.6.1 Setup Inputs

For details on this feature, see 7.3 - Setup System - Setup Inputs.

A.6.2 Setup Common Alarm

For details on this feature, see 7.4 - Setup System - Setup Common Alarm.

Setup Inputs

SETUP INPUTS

Setup input of device

Select input to edit

INPUT DEFINITION

1=DEVICE_1 NO-EV-NL-00:01
2=DEVICE_2 NO-AL-L -00:01
3=DEVICE_3 NC-EV-NL-00:01
4=DEVICE_4 NO-AL-L -00:01
5=DEVICE_5 NC-AL-L -00:01
6=DEVICE_6 NO-EV-NL-00:01
7=DEVICE_7 NO-AL-L -00:01
8=DEVICE_8 NC-EV-NL-00:01
9=RETURN TO SETUP MENU
0=RETURN TO MAIN MENU

SELECT A NUMBER:1

****************************
NO=NORMALLY OPENED
NC=NORMALLY CLOSED

EV=EVENT
AL=ALARMABLE

NL=NOT LATCHED
L =LATCHED

MIN:SEC=DELAY TIME BEFORE

INPUT WILL TRIGGER

NOTE:EVENT CANNOT BE LATCHED
****************************

>CHANGE LABEL(8 CHARACTERS MAX).
>[DEVICE_1]
>[]

>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)?
>[NO]
>[]

>IS INPUT AN ALARM(AL) OR EVENT(EV)?
>[EV]
>[]

>IS ALARM LATCHED-YES(Y) OR NO(N)?
>[N]
>[]

>DELAY TIME BEFORE TRIGGER (MM:SS)?
>[00:01]
>[]

Setup Common Alarm

SETUP COMMON ALARM

Select if the common
alarm relay contact
is to reset with
silence alarm

CURRENT
SETTING

1=SETUP COMMON ALARM

N

2=RETURN TO SETUP MENU
3=RETURN TO MAIN MENU

SELECT A NUMBER:1

>RESET COMMON ALARM WITH SILENCE-YES(Y) OR NO(N)?
>[N]
>[